User Manual

Size = 1 (1 Byte of PF)
Meter Value 1 = 0x63(PF)
Load power factor (PF) = Meter Value 1 =0.99
3. Z-Wave’s Configuration
Configuration
Parameter
Function Size
(Byte)
Value Unit Default Description
1 Watt Meter
Report Period
2 0x01-
0x7FFF
5s 720 720*5s=3600s=1 hour
2 KWH Meter
Report Period
2 0x01-
0x7FFF
10min 6 6*10min=1 hour
3 Threshold of
current for Load
caution
2 10-1300
0.01A
1300 1300*0.01A = 13A
4 Threshold of
KWh for Load
caution
2 1-10000
1KWh
10000
5 Restore switch
state mode
1 0-2 1 0 : Switch off
1 : Last switch state
2 : Switch on
6 Mode of Switch
Off function
1 0-1 1 0 : Disable
1 : Enable
7 LED indication
mode
1 1-2 1 1 : Show switch state
2 : Show night mode
8 Auto off timer
2 0-0x7FFF
1s
0 0 : Disable auto off
function
1-0x7FFF : 1s ~ 32767s
9 RF off com-
mand mode
1 0-3 0 0 : Switch off
1 : Ignore
2 : Switch toggle
3 : Switch on
3-1
Watt
Meter Report Period:
If the setting is configured for 1hour (set value =720), the PAN15 will report its
instant power consumption every 1 hour to Group1 node. The maximum interval
to report its instant power consumption is 45 hours (5s*32767/3600=45hr).
3-2 KWH Meter Report Period:
If the setting is configured for 1hour (set value =6), the PAN15 will report its
Accumulated Power Consumption (KW/h) every 1 hour to Group1 node. The
maximum interval to report its Accumulated Power Consumption (KW/h) is 227.55
days (10min*32767/1440=227.55 days).
3-3 Threshold of current for Load Caution
This is a warning when the current of load over the preset threshold value, if the
setting value is 1300, when the load current of Relay1 over this value, PAN15
will send current meter report to warn the Group1 node, the Range of the setting
value is from 10 to 1300,and the default value is 1300.
3-4 Threshold of KWh for Load Caution
This is a warning when the KWh of load over the preset threshold value, If the
8