Any-Grid™ use with Lithium battery models: Pylontech US2000(C), US3000(C), Phantom-S, Force L1 and Force L2 Applicable for Any-Grid™ PSW-H-5kW-230/48V and PSW-H-5kW-120/48V Recommended battery settings guide
1.0 Introduction This guide outlines the recommended settings and establishing communication for operation of one or more AnyGrid™ PSW-H-5kW-230/48V or PSW-H-5kW-120/48V hybrid inverter chargers with Pylontech US2000, US2000C, US3000, US3000C, Phantom-S, Force L1 and Force L2 battery racks, referred to in this guide as “battery racks”. The US2000C and US3000C batteries are referred to as “C models” in this guide. All connected batteries must be of the same model name.
.0 System Overview Pylontech battery racks 4.0 Battery Sizing To maintain the full battery warranty, each battery rack should be sized not to exceed 25 Adc (37 Adc for the US3000(C), Force L1 and Force L2) continuous current and 100 Adc peak (105 Adc for the Force L1/L2, 200 Adc for the US3000C).
3. Dip Switches location (see note below table for US2000C/US3000C*) Locate the four battery Dip switches as shown above at position ➊ (position may vary on different battery rack models). Each switch can be set ON in the top position or OFF in the bottom position*. Set the Dip switches as follows, depending on the number of battery clusters / groups: Dip 1 Dip 2 Dip 3 Dip 4 Group address All models: Single group only. The master battery rack must have this setting.
PYLON Any-Grid Master Battery Rack For systems with multiple Any-Grids, this connection (marked green) can be made with any of the inverters, but only a single unit.
Please note that standard Ethernet splitters do not work, as they split the 8 pins into two groups of 4, they do not put all pins parallel as required here. Master RS485 port from group 2 is connected to the same hub as the master from group 1 The PSW-H-BAT-CABLE-PYLON(-2) cable is connected to the hub on one side and the PSW-H on the other side. If using the PSW-H-BAT-CABLE-PYLON-2 cable, make sure the “PYLON” label is on the hub side, and the unlabeled end on the Any-Grid side.
Note: Settings menus 02, 26, 27 and 29 are over-written automatically once communication with the battery is established (see step 11). This is to ensure the maximum life expectancy of the battery and to maintain battery warranty. Therefore, these values cannot be changed once menu 05 is set to “PYL”.
6.0 Warning Codes related to Pylontech Batteries The following warning codes will be shown on the PSW-H display if the corresponding events are active. Warning Code Warning Event Audible Alarm 60 Battery charging and discharging temporarily disabled to protect Lithium battery. Beeps once every second 61 Battery communication lost. After 10 minutes of no communication charging and discharging will stop to protect Lithium battery.