PSW-H Installation and User Manual
www.phocos.com    10  | P a g e    
3.  Insert the three AC source wires through the rectangular casing hole (cable gland for 120 Vac models) 
marked “AC INPUT”. Insert the “PE” protective conductor    first into the corresponding AC input terminal 
and tighten with a torque of 1.4 ~ 1.6 Nm (1.0 ~ 1.2 lbf⋅ft). Repeat for the neutral “N” and live “L” conductors. 
PSW-H-5KW-120/48V and PSW-H-6.5KW-120/48V            All other models 
Fig. 7: AC input connection 
4.  Insert the three AC load wires through the rectangular casing hole (cable gland for 120 Vac models) marked 
“AC OUTPUT”. Insert the “PE” protective conductor    first into the corresponding AC output terminal and 
tighten with a torque of 1.4 ~ 1.6 Nm (1.0 ~ 1.2 lbf⋅ft). Repeat for the neutral “N” and live “L” conductors. 
PSW-H-5KW-120/48V and PSW-H-6.5KW-120/48V             All other models 
Fig. 8: AC Output connection 
5.  Make sure the six wires are securely connected. 
CAUTION: Over-tightening the terminal screws can cause damage to the terminal, under-tightening 
can cause a loose connection and excessive heat during operation, make sure to use the prescribed 
torque. Ensure none of the conductor insulation is jammed between the terminal contacts. 
CAUTION: Ensure the polarity is correct on all wires. Failure to do so may cause a short-circuit at the 
AC source when several units are working in parallel operation. 
  PV Connection 
WARNING: Before connecting the PV module array to the PV input of the Any-Grid, install a DC circuit breaker 
between each Any-Grid PV terminal pair and the PV modules. This ensures the inverter can be securely 
disconnected during maintenance and is protected from over-current of the PV modules. PV modules 
produce a dangerous voltage even at low light. Make sure the breaker is open / off for the rest of the 
installation procedure until instructed otherwise. 
WARNING: Ensure the PV cables are sized according to the table below. Inadequate PV cables can cause 
excessive heat or fire during operation. 
CAUTION: Short-circuiting the PV+ to the PV- terminal or any of these terminals to the metal body of the unit 
will cause permanent damage not covered under warranty. 
Recommended PV cable cross-section and DC circuit breaker rating: 
Any-Grid model 
PSW-H-5KW-230/48V 
PSW-H-3KW-230/24V 
PSW-H-3KW-120/24V 
PSW-H-5KW-120/48V 
PSW-H-6.5KW-120/48V 
PV cable cross-section 
2.5 ~ 16 mm², AWG 5 ~ AWG 13 
4 ~ 6 mm², AWG 10 ~ AWG 12 
Circuit breaker rating 
30 Adc, min. 450 Vdc 
30 Adc, min. 250 Vdc 
25 Adc, min. 250 Vdc 
per PV input 










