PSW-H Installation and User Manual

www.phocos.com 21 | P a g e
Screen of Units on Phase L1
Screen of Units on Phase L2
9. If there are no further faults displayed, the split-phase system installation is complete. The breakers on the
AC output of each unit can be switched on and then loads may be connected.
6.0 BLE Communication
This unit is equipped with wireless BLE functionality. Download the
“PhocosLink MobileApp from the Google Play™ store or Apple’s App
Store® with an Android™ or iOS device, respectively. Once the App is
installed, use pair your device” with the built-in BLE functionality of your
device to connect to the Any-Grid unit with the BLE pairing password
“123456”. Then open the app and connect to the Any-Grid. The typical
maximum communication distance is approximately 6 ~ 7 meters.
7.0 Relay Contact
There is one potential-free relay contact (3A / 250 Vac) available on the display module (Fig. 2 ). It may be used
to signal an external device when battery voltage reaches a low level, such as a gasoline or diesel generator. The relay
may be wired with normally closed (NC) or normally open (NO) logic. The table below indicates the relay states
between the common (C) and NO, as well as between C and NC contacts.
Any-Grid Status
Condition
Relay terminals:
NC & C
NO & C
Powered Off or
Battery-free mode
Unit is off and AC output is not powered.
Closed
Open
Powered On
Output is
powered
from
Battery
power or
Solar
power.
Settings Menu 01
set as “Utility / AC
input first (USB)
or “Solar / PV first”
(SUB)
Battery voltage < Low DC warning
voltage (2 Vdc for the 48 V model / 1
Vdc for the 24 V model above the
value in settings menu 29)
Open
Closed
Battery voltage > Settings menu 13
or battery charging reaches Floating
phase
Closed
Open
Settings Menu 01
is set as SBU
Battery voltage < Settings menu 12
Open
Closed
Battery voltage > Settings menu 13
or battery charging reaches Floating
phase
Closed
Open