PSW-H Installation and User Manual
www.phocos.com    26  | P a g e    
01 
AC output source priority: 
Configure the priority of 
which power sources supply 
the AC output load 
Utility / AC input first (Default) 
“USB” for: 
Utility → Solar → Battery 
AC input / utility will provide power 
to the loads as first priority. If there 
is excess solar power beyond what 
is required for battery charging, 
this power is used to supply power 
to the loads instead. The battery is 
not discharged (Grid mode). 
Solar and battery will provide 
power to the loads when AC input / 
utility power is unavailable (Off-
Grid mode). 
Solar / PV first 
“SUB” for: 
Solar → Utility → Battery 
Solar provides power to the loads 
as first priority. If solar power is not 
sufficient to power all connected 
loads, AC input / utility power will 
supply the loads simultaneously 
(Grid mode). 
If no solar power is available (ex. at 
night), AC input / utility power is 
used exclusively. The battery is only 
discharged when the AC input / 
utility power is unavailable (Off-
Grid mode). 
SBU priority 
“SBU” for: 
Solar → Battery → Utility 
Solar powers the loads as first 
priority. If solar power is not 
sufficient to power all connected 
loads, the battery will supply power 
to the loads at the same time. The 
Any-Grid is disconnected from the 
grid at this time (Off-Grid mode). 
AC input / utility provides power to 
the loads (Grid mode) only when 
the battery voltage drops to either 
low-level warning voltage or the 
setting point in settings menu 12. 
When first applying SBU priority, it 
may take up to 10 minutes for the 
Any-Grid to switch to Off-Grid 
mode. 
02 
Maximum total battery 
charging current of AC and 
solar charging combined: 
Max. total charging current = 
AC input charging current + 
solar charging current 
This setting is important to 
limit charging current for 
some battery types. 
10A 
80A (Default) 
Can be set from 10 ~ 80 Adc (up to 120 Adc for PSW-H-6.5KW-120/48V) 
in 10 Adc increments. This is the battery-side DC charging current. 
03 
AC input voltage range 
Appliances   
Accepted AC input voltage range 
from 90 ~ 280 Vac for 230 Vac 
models, 80 ~ 140 Vac for 120 Vac 
models. 