PSW-H Installation and User Manual

www.phocos.com 28 | P a g e
09
AC output frequency
Only relevant for Off-Grid
mode
50 Hz (Default, 230 Vac models)
60 Hz (Default, 120 Vac models)
10
AC output voltage
Only relevant for Off-Grid
mode
Note: To avoid damage, this
value can only be changed if
the inverter is in Stand-By
mode (AC output turned off).
See chapter Installing
Multiple Units in Parallel,
Split Phase or 3-Phase
Configuration for detailed
instructions.
230 Vac (Default, 230 Vac
models)
From 220 ~ 240 Vac in 10 Vac
increments for 230 Vac models.
110, 120 and 127 Vac for 120 Vac
models, default 120 Vac.
11
Maximum AC source charging
current (battery side)
If settings menu 02 is smaller
than this value, charging will
be limited by the value in
settings menu 02.
30 Adc (Default)
Available values: 2 Adc and 10 ~ 80
Adc (up to 120 Adc for PSW-H-
6.5KW-120/48V) in 10 Adc
increments.
12
Voltage set-point to switch
from Off-Grid mode to Grid
mode when “SBU priority is
selected in settings menu 01.
This may be a percentage for
some battery types selected
in setting menu 05.
48 Vdc (48 Vdc model Default)
24 Vdc (24 Vdc model Default)
Available values: 44 ~ 57 Vdc in 1
Vdc increments for 48 Vdc model.
Available values: 22 ~ 28.5 Vdc in
0.5 Vdc increments for 24 Vdc
model.
13
Voltage set-point to switch
from Grid mode to Off-Grid
mode when selecting “SBU
priority in settings menu 01.
Battery fully charged
54 Vdc (48 Vdc model Default)
27 Vdc (24 Vdc model Default)
Available values: “FULL and 48 ~ 64 Vdc in 1 Vdc increments for 48 Vdc
model.
Available values: “FULL and 24 ~ 32 Vdc in 1 Vdc increments for 24 Vdc
model.
The battery is considered fully charged when the float charging phase
is reached.
16
Battery charger source priority
Configure the priority of
which power sources are used
to charge the battery. The AC
Solar first
Solar power will charge battery as
first priority.
Utility will charge battery only
when solar energy is not available
and the unit is in Grid mode.