Low voltage disconnect 
The AC output is turned off 
when the battery reaches this 
voltage level to protect the 
battery from deep discharge. 
The low DC / battery warning 
voltage is 2 Vdc for the 48 V 
model and 1 Vdc for the 24 V 
model above this setting. 
Note: It is necessary for each 
unit to have a PV array or AC 
source connected to wake up 
after a low voltage disconnect 
event. 
44.0 Vdc (48 Vdc model Default) 
22.0 Vdc (24 Vdc model Default) 
If “User-defined” is selected in 
settings menu 05, this value can be 
changed. 
Available values: 37.5 ~ 54.0 Vdc in 
0.1 Vdc increments for 48 Vdc 
model. 
Available values: 18.8 ~ 27.0 Vdc in 
0.1 Vdc increments for 24 Vdc 
model. 
This voltage is fixed and 
independent of the load power 
level. 
30 
Low voltage reconnect 
If the AC output is turned off 
due to low voltage disconnect 
(settings menu 29), the AC 
output is automatically turned 
back on once this voltage is 
reached. This value must be at 
most 0.5 Vdc below settings 
menu 27, and at least 4 Vdc for 
the 48 V model or 2 Vdc for 
the 24 V model higher than 
settings menu 29. 
Note: It is necessary for each 
unit to have a PV array or AC 
source connected for low 
voltage reconnect to function. 
54.7 Vdc (48 Vdc model Default) 
27.1 Vdc (24 Vdc model Default) 
If “User-defined” is selected in 
settings menu 05, this value can be 
changed. 
Available values: 41.6 ~ 63.5 Vdc in 
0.1 Vdc increments for 48 Vdc 
model. 
Available values: 20.9 ~ 31.5 Vdc in 
0.1 Vdc increments for 24 Vdc 
model. 
32 
Boost battery charging 
duration 
The duration for which the 
boost voltage from settings 
menu 26 is held before the 
Floating phase is reached.   
Automatic 
120 min (Default) 
If “User-defined” is selected in settings menu 05, this value can be 
changed. Available values: “Automatic” and 5 ~ 900 minutes in 5 min. 
increments. 
If “Automatic” is set, the duration of bulk phase (see chapter 
“Specifications”  → “Battery Charging”) is multiplied by 10, with a 
minimum of 10 minutes and maximum of 8 hours. 
33 
Battery equalization 
Battery equalization helps 
prevent sulfation of lead-acid 
batteries and is beneficial for 
bringing all cells to the same 
voltage. Consult your battery 
manual to make sure the 
battery can withstand the 
higher voltages required for 
this purpose. This is typically 
the case for flooded lead-acid 
batteries. 
Enabled 
Disabled (Default) 
If “User-defined” or “Flooded” is selected in settings menu 05, this value 
can be changed. 