PSW-H Installation and User Manual
www.phocos.com    50  | P a g e    
Buzzer beeps 
continuously and red 
LED is on. 
Fault code 07 
Overload error. Inverter is 
overloaded ≥110% for more 
than allowed duration. 
Reduce the connected load by 
switching off some equipment. 
Fault code 05 
Output short circuited. 
Check if wiring is connected well 
and remove abnormal loads. 
Temperature of internal 
converter components is 
over 120°C. 
Check whether the air flow of the 
unit is blocked or whether the 
ambient temperature is too high. 
Fault code 02 
Temperature of inverter 
components is over 100°C. 
Fault code 03 
Battery is over-charged.   
Return to repair center. 
The battery voltage is too 
high. 
Check if specifications and quantity 
of batteries meet requirements. 
Fault code 01 
Fan fault 
Replace the fan(s) 
Fault code 06/58 
AC output abnormal 
1. Reduce the connected load. 
2. Return to repair center 
Fault code 
08/09/53/57 
Internal components failed. 
Return to repair center. 
Fault code 51 
Over current or surge. 
Restart the unit, if the error occurs 
again, please return to repair center. 
Fault code 52 
Internal DC bus voltage too 
low. 
Fault code 55 
Output voltage 
unbalanced. 
Fault code 56 
Battery not connected cor-
rectly / internal fuse blown. 
If the battery is connected correctly, 
please return to repair center. 
Fault code 13 
Battery discharge over-
current detected. 
Increase the battery discharge 
current limit in settings menu 
number 41. 
Warning code 60 
Battery discharging and 
charging temporarily 
disabled by battery 
management system. 
Battery is not allowed to discharge 
and charge as the battery 
management system (BMS) in the 
connected battery has blocked 
discharging and charging due a BMS 
error. The Any-Grid will stop 
discharging and charging the 
battery. 
Warning code 61 
Battery management 
system communication 
loss. 
This fault is only available when the 
battery type in settings menu 05 is 
set to anything other than “AGM”, 
“Flooded” or “User-defined”. Unless 
you are using a BMS connection for 
a compatible lithium battery and 
have correctly configured the 
connection, make sure to use “AGM”, 
“Flooded” or “User-defined” in 
settings menu 05. 
After battery communication cable 
is connected and a communication 
signal is not detected for 3 minutes, 
buzzer will beep. After 10 minutes, 
inverter will stop charging and 
discharging the battery. 