Fault code 84 
The detected AC input 
voltage and frequency 
differ between units. 
1.  Check the AC input wiring 
connection and restart the unit. 
2.  Make sure the AC source starts 
up with the same voltage and 
frequency on each phase. If there 
are breakers installed between 
AC inout and Any-Grid units, 
please be sure all breakers can be 
turned on the AC input at same 
time. 
3.  If the problem still remains, 
please contact your repair center. 
Fault code 85 
AC output current 
unbalanced 
1.  Restart the inverter. 
2.  Remove excessive loads and re-
check load information from LCD 
of units. If the values are different 
between units on the same 
phase, please check if AC input 
and output cables are the same 
length, cross-section and 
material. 
3.  If the problem remains, please 
contact your repair center. 
Fault code 86 
AC output mode setting 
is different between units. 
1.  Switch off the units and check 
settings menu number 28. 
2.  For parallel systems on a single 
phase, make sure each unit is set 
to “PAL” in settings menu number 
28. 
For plit-phase and 3-phase 
systems, make sure each unit has 
the same two first characters in 
settings menu number 28 (“2P” 
for split-phase “3P” for 3-phase) 
and is on the correct phase. 
3.  If the problem remains, please 
contact your repair center. 
Fault code 90 
EEPROM corrupted 
Please contact your repair center and 
communicate the serial number of 
the affected unit. 
12.0  Specifications 
  Grid Mode 
Model 
PSW-H-5KW-
230/48V 
PSW-H-3KW-
230/24V 
PSW-H-5KW-
120/48V 
PSW-H-6.5KW-
120/48V 
PSW-H-3KW-
120/24V 
AC Input Voltage Waveform 
Pure Sine Wave (utility or generator) 
Nominal AC Input Voltage 
230 Vac 
120 Vac 
Maximum AC Input Current 
40 Aac 
30 Aac 
60 Aac 
38.3 Aac 