PSW-H Installation and User Manual
www.phocos.com    55  | P a g e    
AC Output Power De-
Rating in Off-Grid Mode 
If the AC output load power 
is higher than the power in 
the diagram to the right, 
the AC output voltage will 
be decreased until the AC 
output power reaches the 
de-rated power specified to 
conserve battery. The lower 
limit of the AC output 
voltage de-rating is -20 / 
-40 Vac for 120 Vac models 
and 230 Vac models, 
respectively, compared to 
the nominal AC output 
voltage setting. For the 
PSW-H-6.5KW-120/48V the 
lower limit of the AC output 
de-rating is 95% x the 
nominal AC output voltage 
setting. 
  Battery Charging 
Charging from AC Source 
Model 
PSW-H-5KW-
230/48V 
PSW-H-3KW-
230/24V 
PSW-H-5KW-
120/48V 
PSW-H-6.5KW-
120/48V 
PSW-H-3KW-
120/24V 
Max. Battery Charging 
Current at Nominal AC 
Input Voltage 
80 Adc 
120 Adc 
80 Adc 
Boost 
Charging 
Voltage 
Flooded Battery 
58.4 Vdc 
29.2 Vdc 
58.4 Vdc 
29.2 Vdc 
AGM / Gel 
Battery 
57.6 Vdc 
28.8 Vdc 
57.6 Vdc 
28.8 Vdc 
Floating Charging Voltage 
55.2 Vdc 
27.6 Vdc 
55.2 Vdc 
27.6 Vdc 
Overcharge Protection 
66 Vdc 
33 Vdc 
66 Vdc 
33 Vdc 
Charging Algorithm 
4-Stage with Equalization 
Charging Curve 
If battery type “User-
defined” is set in chapter 
“Device Operation 
Settings” → “Settings 
menu 05”, the charging 
parameters are set with the 
following settings menus: 
Charge current limit: 11 
Boost voltage: 26 
Boost duration: 32 
Float voltage: 27 
Equalization: 33, 34, 35, 36, 
37 
Battery voltage for 
24 Vdc / 48 Vdc 
model 
AC Output Power 
Nominal Power 
Nominal Power x 0.8 
18.8 / 37.5 Vdc     25 / 50 Vdc* 
Battery Voltage & Current 
Bulk: phase 1 
(charge current limited) 
Absorption or 
Equalization: phase 2/3 
(boost or equalization 
voltage limited) 
Floating: phase 4 
(float voltage limited) 
Time 
Voltage 
Current 
*48 Vdc for PSW-H-6.5KW-120/48V 