Datasheet

HDFK 4 Order No.: 0707086
http://eshop.phoenixcontact.se/phoenix/treeViewClick.do?UID=0707086
Phoenix Contact AB Page 2 / 6
http://www.phoenixcontact.se Nov 6, 2012
Dimensions
Width 8.1 mm
Technical data
Rated surge voltage 6 kV
Pollution degree 3
Surge voltage category III
Insulating material group I
Connection in acc. with standard IEC 60947-7-1
Nominal current I
N
32 A
Nominal voltage U
N
400 V (With metal panels of 1 mm ... 2.5 mm)
250 V (With metal panels over 2.5 mm ... 4 mm)
400 V (With plastic panels of 1 mm ... 4 mm)
Open side panel nein
Number of positions 2
Shock protection test specification DIN EN 50274 (VDE 0660-514):2002-11
Back of the hand protection guaranteed
Finger protection guaranteed
Surge voltage test setpoint 4.8 kV
Result of surge voltage test Test passed
Power frequency withstand voltage setpoint 1.5 kV
Result of power-frequency withstand voltage test Test passed
Checking the mechanical stability of terminal
points (5 x conductor connection)
Test passed
Bending test rotation speed 10 rpm
Bending test turns 135
Bending test conductor cross section/weight 0.2 mm² / 0.2 kg
4 mm² / 0.9 kg
6 mm
2
/ 1.4 kg
Result of bending test Test passed
Conductor cross section tensile test 0.2 mm²
Tractive force setpoint 10 N
Conductor cross section tensile test 4 mm²
Tractive force setpoint 60 N
Conductor cross section tensile test 6 mm²
Tractive force setpoint 80 N