Datasheet

https://www.phoenixcontact.com/gb/products/1039830
04/10/2019Page2/5
Power supply unit-TRIO-PS-IP67/1AC/24DC/20-1039830
Technical data
Ambient conditions
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Climatic class 3K3 (in acc. with EN 60721)
Degree of pollution 4
Installation height ≤ 4000 m (> 2000 m, Derating: 10 %/1000 m)
Input data
Nominal input voltage range 100 V AC ... 240 V AC
110 V DC ... 250 V DC
Input voltage range 100 V AC ... 240 V AC 10%
110 V DC ... 250 V DC 10%
Dielectric strength maximum ≤ 300 V AC 15 s
AC frequency range 50 Hz ... 60 Hz
Discharge current to PE < 3.5 mA
Current consumption 5.6 A (100VAC)
2.4 A (240 V AC)
Nominal power consumption 36.8 W
Inrush surge current typ. 20 A (at 25°C)
Mains buffering typ. 10 ms (120 V AC)
typ. 15 ms (230 V AC)
Input fuse 10 A (internal (device protection))
Choice of suitable circuit breakers 10 A ... 16 A (Characteristics B, C, D, K)
Type of protection Transient surge protection
Protective circuit/component Varistor
Output data
Nominal output voltage 24 V DC ±1%
Nominal output current (I
N
)
20 A
Dynamic Boost (I
Dyn.Boost
)
30 A (5 s)
Derating > 60 °C ... 70 °C (2.5%/K)
Output overvoltage protection ≤ 30 V DC
Control deviation < 1 % (change in load, static 10 % ... 90 %)
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
< 0.1 % (change in input voltage ±10 %)
Residual ripple
≤ 30 mV
PP
Output power 480 W
Typical response time < 1 s
Maximum power dissipation in no-load condition < 3 W (120 V AC)
< 2.5 W (230 V AC)
Power loss nominal load max. < 48 W (120 V AC)
< 36 W (230 V AC)
General