Datasheet

https://www.phoenixcontact.com/gb/products/1039830
04/10/2019Page3/5
Power supply unit-TRIO-PS-IP67/1AC/24DC/20-1039830
Technical data
General
Net weight 3.7 kg
Efficiency 91 % (100VAC)
93 % (230 V AC)
Insulation voltage input/output 4 kV AC (type test)
1.5 kV AC (routine test)
Protection class I
Degree of protection IP67
MTBF (IEC 61709, SN 29500) > 1400000 h (25°C)
> 800000 h (40 °C)
> 400000 h (60 °C)
Assembly instructions
Alignable: 20mm horizontally, 50mm vertically above, 100mm vertically
below
Connection data, input
Connection method Circular connector
Connection data, output
Connection method Circular connector
Connection data for signaling
Connection method Circular connector
Standards and Regulations
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Noise emission EN 55011 (EN 55022)
Noise immunity
Immunity according to EN 61000-6-1 (residential), EN 61000-6-2
(industrial)
Standards/regulations EN 61000-4-2
Contact discharge 4 kV (Test Level 2)
Standards/regulations EN 61000-4-3
Frequency range 80 MHz ... 1 GHz
Test field strength 10 V/m (Test Level 3)
Frequency range 1.4 GHz ... 2 GHz
Test field strength 3 V/m (Test Level 2)
Standards/regulations EN 61000-4-4
Comments Criterion B
Standards/regulations EN61000-6-3
EN61000-4-6
Frequency range 0.15 MHz ... 80 MHz
Voltage 10 V (Test Level 3)
Conducted noise emission EN 55016 EN61000-6-4 (Class A)
Standards/regulations EN 61000-4-11
Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Standard - Electrical safety IEC61010-2-201(SELV)