Redundancy module, with protective coating-QUINT4-S-
ORING/12-24DC/1X40/VP-1043418
Technical data
Dimensions
Depth with alternative assembly 35 mm
Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -40 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) ≤ 100 % (at 25 °C, non-condensing)
Climatic class 3K3 (in acc. with EN 60721)
Degree of pollution 2
Installation height ≤ 5000 m (> 2000 m, observe derating)
Input data
Nominal input voltage range 12 V DC ... 24 V DC
Input voltage range 8 V DC ... 27.5 V DC (SELV)
Current consumption 40 A
Nominal input current 40 A (-40°C...60°C)
Output data
Output voltage range 8 V DC ... 27.5 V DC
Nominal output current (I
N
)
40 A
Static Boost (I
Stat.Boost
)
45 A
Dynamic Boost (I
Dyn.Boost
)
60 A (5 s)
Selective Fuse Breaking (I
SFB
)
215 A (15 ms)
Derating 60 °C ... 70 °C (2.5%/K)
Connection in series No
Output overvoltage protection ≤ 30 V DC
Power loss nominal load max.
6.5 W (I
OUT
= 40 A)
6 W (I
OUT
= 40 A)
General
Net weight 0.4 kg
Efficiency typ. 99 % (12 V DC)
typ. 99.2 % (24 V DC)
Protection class III
Degree of protection IP20
MTBF (IEC 61709, SN 29500) > 13486000 h (25°C)
> 7314000 h (40 °C)
> 3379000 h (60 °C)
Mounting position horizontal DIN rail NS 35, EN 60715
Assembly instructions
alignable: P
N
≥50%, 5mm horizontally, 15mm next to active
components, 50mm vertically