Redundancy module, with protective coating-QUINT4-S-
ORING/12-24DC/1X40/VP-1043418
Technical data
Standards and Regulations
Standards/regulations EN 61000-4-3
Frequency range 80 MHz ... 1 GHz
Test field strength 10 V/m (Test Level 3)
Frequency range 1.4 GHz ... 2 GHz
Test field strength 3 V/m (Test Level 2)
Standards/regulations EN 61000-4-4
Comments Criterion B
Standards/regulations EN61000-4-6
Frequency range 0.15 MHz ... 80 MHz
Voltage 10 V (Test Level 3)
Conducted noise emission EN 55016 EN61000-6-4 (Class A)
Standards/regulations EN 61000-4-8
Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Standard - Electrical safety EN 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power installations
and their assembly into electrical power installations
EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage IEC60950-1 (SELV) and EN60204-1 (PELV)
Standard - Safe isolation DIN VDE 0100-410
Standard – Protection against shock currents, basic requirements for
protective separation in electrical equipment
EN 50178
UL approvals UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D
(Hazardous Location)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.
ATEX  II 3 G Ex nA nC IIC Gc
SIQ 17 ATEX 020 U
IECEx Ex nA nC IIC Gc
IECEx SIQ 17.0006U
Environmental Product Compliance
REACh SVHC Lead 7439-92-1
Drawings