Datasheet

https://www.phoenixcontact.com/gb/products/1064922
06/18/2019Page4/6
Power supply unit-EM-CPS-PS/3AC/24DC/5-1064922
Technical data
Standards and Regulations
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Noise emission EN 55011 (EN 55022)
Noise immunity Immunity according to EN 61000-6-2 (industrial)
Standards/regulations EN 61000-4-2
Contact discharge 4 kV (Test Level 2)
Standards/regulations EN 61000-4-3
Frequency range 80 MHz ... 1 GHz
Test field strength 10 V/m (Test Level 3)
Frequency range 1.4 GHz ... 2 GHz
Test field strength 3 V/m (Test Level 2)
Standards/regulations EN 61000-4-4
Comments Criterion B
Standards/regulations EN 61000-6-4
EN61000-6-2
Conducted noise emission EN 55016 EN61000-6-4 (Class A)
Standards/regulations EN 61000-4-11
Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Standard - Safety of transformers EN 61558-2-16 (air clearances and creepage distances only)
Standard - Electrical safety IEC61010-1 (SELV)
Standard – Electronic equipment for use in electrical power installations
and their assembly into electrical power installations
EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage IEC61010 (SELV) / (PELV)
Standard - Safe isolation DIN VDE 0100-410
Standard – Limitation of mains harmonic currents EN61000-3-2
UL approvals UL Listed UL 61010-2-201
Shock 18 ms, 30g, in each space direction (according to IEC60068-2-27)
Vibration (operation)
10...150Hz, amplitude ±0.35mm, 5g, 90min. (in accordance with IEC
60068-2-6)
2Hz...15Hz, amplitude ±1mm, >15Hz, 0.7g (in accordance with DNV
GL Class A)
Overvoltage category (EN 61010-1) II
Drawings
Block diagram
L1
L2
L3
13
14
+
+
-
-
-
1.1
1.2
1.3
TRIO CROSS POWER
2.1
2.2
2.3
2.4
2.5
3.1
3.2