Datasheet

https://www.phoenixcontact.com/gb/products/1065313
07/23/2019Page2/6
Surge protection device-TTC-6P-3-HF-12DC-PT-I-1065313
Technical data
General
Mounting type DIN rail: TH 35 - 7.5 mm
Type DIN rail module, two-section, divisible
Direction of action
Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-
Earth Ground
Protective circuit
IEC test classification C1
C2
C3
D1
Nominal voltage U
N
12 V DC
Maximum continuous voltage U
C
15 V DC
10 V AC
Rated current 600 mA (56 °C)
Operating effective current I
C
at U
C
≤ 100 µA
Residual current I
PE
≤ 200 µA
Nominal discharge current I
n
(8/20) µs (line-line)
5 kA
Nominal discharge current I
n
(8/20) µs (line-earth)
5 kA
Pulse discharge current I
imp
(10/350)µs (line-line)
0.5 kA
Pulse discharge current I
imp
(10/350)µs (line-earth)
0.5 kA
Total discharge current I
total
(8/20)µs
10 kA
Voltage protection level U
p
(line-line)
≤ 145 V (C1 - 1 kV/500 A)
≤ 260 V (C2 - 10 kV / 5 kA)
≤ 25 V (C3 - 25 A)
≤ 30 V (C3 - 100 A)
Voltage protection level U
p
(line-earth)
≤ 80 V (C1 - 1 kV/500 A)
≤ 95 V (C2 - 10 kV / 5 kA)
≤ 25 V (C3 - 25 A)
≤ 30 V (C3 - 100 A)
Voltage protection level U
p
static (line-line)
≤ 40 V (C1 - 1 kV/500 A)
≤ 95 V (C2 - 10 kV / 5 kA)
Voltage protection level U
p
static (line-earth)
≤ 40 V (C1 - 1 kV/500 A)
≤ 95 V (C2 - 10 kV / 5 kA)
Response time t
A
(line-line)
≤ 1 ns
Response time t
A
(line-earth)
≤ 1 ns
Input attenuation aE, sym. typ. 0.3 dB (≤ 8.7 MHz / 150 Ω)
Input attenuation aE, asym. typ. 0.3 dB (≤ 10.5 MHz / 150 Ω)
Cut-off frequency fg (3 dB), sym. in 150 Ohm system typ. 60 MHz
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ohm system typ. 60 MHz
Capacity (line-line) typ. 32 pF
Capacity (line-earth) typ. 32 pF