Datasheet

https://www.phoenixcontact.com/gb/products/1065313
07/23/2019Page3/6
Surge protection device-TTC-6P-3-HF-12DC-PT-I-1065313
Technical data
Protective circuit
Resistance in series 1.65 Ω ±20 %
Max. required back-up fuse 630 mA (FF)
Impulse durability (line-line) C1 - 1kV / 500A
C2 - 10kV / 5kA
C3 - 100A
Impulse durability (line-earth) C1 - 1kV / 500A
C2 - 10kV / 5kA
C3 - 100A
D1 - 500A
Pulse reset time (line-line) ≤ 30ms
Pulse reset time (line-earth) ≤ 30ms
Additional technical data
Max. total discharge current I
total max
(8/20)µs
20 kA (1x)
Connection data
Connection method Push-in connection
Stripping length 8 mm
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section solid 0.2 mm² ... 4 mm²
Conductor cross section AWG 24 ... 12
Standards and Regulations
Standards/specifications IEC61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012
EN61643-21 2001 + A1:2009 + A2:2013
Environmental Product Compliance
REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”,
Category “Manufacturer's declaration”
Classifications
eCl@ss
eCl@ss 6.0 27130800
eCl@ss 7.0 27130807
eCl@ss 8.0 27130807
eCl@ss 9.0 27130807
ETIM
ETIM 5.0 EC000943
ETIM 6.0 EC000943