Datasheet

https://www.phoenixcontact.com/gb/products/1065317
07/23/2019Page2/6
Surge protection device-TTC-6P-1X2-F-24DC-UT-I-1065317
Technical data
General
Mounting type DIN rail: TH 35 - 7.5 mm
Type DIN rail module, two-section, divisible
Direction of action
Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-
Earth Ground
Protective circuit
IEC test classification C1
C2
C3
D1
Nominal voltage U
N
24 V DC
Maximum continuous voltage U
C
30 V DC
21 V AC
Rated current 600 mA (56 °C)
Operating effective current I
C
at U
C
≤ 5 µA
Residual current I
PE
≤ 1 µA
Nominal discharge current I
n
(8/20) µs (line-line)
5 kA
Nominal discharge current I
n
(8/20) µs (line-earth)
5 kA
Nominal discharge current I
n
(8/20) µs (core-signal ground)
5 kA
Pulse discharge current I
imp
(10/350)µs (line-line)
0.5 kA
Pulse discharge current I
imp
(10/350)µs (line-earth)
0.5 kA
Pulse discharge current I
imp
(10/350)µs (line-signalground)
0.5 kA
Total discharge current I
total
(8/20)µs
10 kA
Voltage protection level U
p
(line-line)
≤ 200 V (C1 - 1 kV/500 A)
≤ 320 V (C2 - 10 kV / 5 kA)
≤ 50 V (C3 - 25 A)
≤ 55 V (C3 - 100 A)
Voltage protection level U
p
(line-earth)
≤ 900 V (C1 - 1 kV/500 A)
≤ 1.05 kV (C2 - 10 kV / 5 kA)
≤ 1.3 kV (C3 - 25 A)
≤ 1.4 kV (C3 - 100 A)
Voltage protection level U
p
(line-signalground)
≤ 750 V (C1 - 1 kV/500 A)
≤ 750 V (C2 - 10 kV / 5 kA)
≤ 700 V (C3 - 25 A)
≤ 750 V (C3 - 100 A)
Voltage protection level U
p
static (line-line)
≤ 50 V (C1 - 1 kV/500 A)
≤ 120 V (C2 - 10 kV / 5 kA)
Voltage protection level U
p
static (line-earth)
≤ 900 V (C1 - 1 kV/500 A)
≤ 1.05 kV (C2 - 10 kV / 5 kA)
Voltage protection level U
p
static (line-signalground)
≤ 750 V (C1 - 1 kV/500 A)
≤ 750 V (C2 - 10 kV / 5 kA)