Brochure

No. of pos. Dim. a
[mm]
2 5.00
3 10.00
4 15.00
5 20.00
6 25.00
7 30.00
8 35.00
9 40.00
10 45.00
11 50.00
12 55.00
13 60.00
14 65.00
15 70.00
16 75.00
528 PHOENIX CONTACT
Notes:
In accordance with DIN EN 61984, COMBICON connectors have
no switching power. During designated use, they must not be
plugged in or disconnected when carrying voltage or under load.
COMBICON select
Possible combinations for plug-in connectors can be found in
COMBICON select at www.phoenixcontact.net/catalog or
starting on page 506.
Recommended assembly available if required
1
) When using ferrules, 250 V is only achieved in combination with
surge voltage category/pollution degree II/2.
High terminal block capacity thanks to
rectangular terminal block space
5.0 mm pitch
Tension sleeve principle/highly flexible
conductor protection
Connectors can be plugged in horizon-
tally
Connectors with a rugged and reliable
contact system
Monoblock design
Connectors with screw connection up
to 2.5 mm
2
Technical data
PT 1,5/...-PH-5,0 PT 1,5/...-PH-5,0 CLIP PT 1,5/...-PVH-5,0
Technical data according to IEC/DIN VDE
Rated current / conductor cross section [A] / [mm²] 10 / 1.5 10 / 1.5 12 / 1.5
Rated insulation voltage for pollution degree 2 [V] 400 400 320
Pitch [mm] 5 5 5
Connection capacity
Solid / stranded [mm²] / [mm²] / AWG 0.2 - 2.5 / 0.2 - 2.5 / 26 - 12 0.2 - 1.5 / 0.2 - 1.5 / 26 - 14 0.2 - 2.5 / 0.2 - 2.5 / 26 - 14
Stranded with ferrules without plastic sleeve [mm
2
] 0.25 - 1 0.25 - 1 0.25 - 1.5
1
)
Stranded with ferrules with plastic sleeve [mm
2
] 0.25 - 1 0.25 - 1 0.25 - 1.5
1
)
Multi-conductor connection capacity (two conductors with the same cross section)
Solid / stranded [mm
2
] - / - - / - 0.2 - 0.75 / 0.2 - 0.75
Stranded with ferrules without plastic sleeve [mm
2
] - - 0.25 - 0.34
1
)
Stranded with TWIN ferrule with plastic sleeve [mm
2
] - - 0.5 - 0.75
1
)
Insulation coordination
Surge voltage category / pollution degree III / 3 III / 2 II / 2 III / 3 III / 2 II / 2 III / 3 III / 2 II / 2
Rated insulation voltage [V] 250 400 630 250 400 630 250 320 630
Rated surge voltage [kV] 4 4 4 4 4 4 4 4 4
Approval data (UL/CUL) Use Group B C D B C D B C D
Nominal voltage [V] 300 - 300 300 - 300 300 - 300
Nominal current [A] 5 - 5 5 - 5 15 - 10
Connection capacity AWG AWG 28 - 14 - 28 - 14 28 - 14 - 28 - 14 26 - 12 - 26 - 12
Approval data (CSA) Use Group B C D B C D B C D
Nominal voltage [V] 300 - 300 300 - 300 - - -
Nominal current [A] 5 - 5 5 - 5 - - -
Connection capacity AWG AWG 26 - 14 - 26 - 14 26 - 14 - 26 - 14 - - -
General data
Stripping length [mm] 6 6 5
Tightening torque [Nm] 0.35 - 0.4 0.35 - 0.4 0.35 - 0.4
Type of insulation material / insulation material group PA / I PA / I PA / I
Inflammability class according to UL 94 V0 V0 V0
For all types Type Page
Screwdriver
SZS 0,6 x 3,5
Order No.
1205053
Only for PT 1,5/...-PH-5,0 (CLIP)
Keying profile
CP-PTDA
Order No.
1731361
38
Only for PT 1,5/...-PVH-5,0
Keying profile
CP-PT 1,5
38
Accessories
100806040200
0
2
1
3
2
4
8
10
12
14
16
18
6
1
2
3
= 2-pos.
= 5-pos.
= 16-pos.
20
Ambient temperature [°C]
Current strength [A]
Representative derating curve
Type: PT 1,5/...-PH-5,0 CLIP with PST 1,3/...-5,0
Derating curve, determined according to DIN EN 61984 (VDE 0627):2002-09
Representation in accordance with DIN EN 60512-5-2:2003-01
Connected conductor cross section = 1.5 mm
2
Reduction factor = 0.8
Number of positions: See diagram