Technical data
Output data
Load/output load current output
< 300 Ω
Switching output
Output name
No switching output
Power supply
Nominal supply voltage
24 V DC
Supply voltage range
20 V DC ... 30 V DC
Max. current consumption
((30 + I
OUT
) mA)
Power consumption
1.65 W
Connection data
Conductor cross section solid min.
0.25 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section AWG/kcmil min.
24
Conductor cross section AWG/kcmil max
12
Stripping length
10 mm
General
Maximum transmission error
<± 1 % (of final value)
Temperature coefficient, typical
0.02 %/K (0 ... 60°C)
Temperature coefficient, typical
0.04 %/K (-40 ... 65°C)
Linearity error
<± 1 % (From the range end value)
Step response (10-90%)
150 ms
Surge voltage category
III
Pollution degree
2
Rated insulation voltage
300 V AC
Test voltage input/output
3.5 kV (50 Hz, 1 min.)
Test voltage input/power supply
3.5 kV (50 Hz, 1 min.)
Noise emission
EN 61000-6-4
Noise immunity
EN 61000-6-2
Color
green
Housing material
Frianyl B63 V0 GV30
Conformance
CE-compliant
UL, USA / Canada
UL/C-UL listed UL 508
classifications
eCl@ss
eCl@ss 4.0
27200303
eCl@ss 4.1
27200303
eCl@ss 5.0
27200303