Datasheet

https://www.phoenixcontact.com/us/produkte/2313452
Nov 14, 20133/11
Interface converters-FL COMSERVER UNI
232/422/485-2313452
Technical data
Serial interface
Serial transmission speed
0.3; 0.6; 1.2; 2.4; 4.8; 7.2; 9.6; 19.2; 38.4; 57.6; 115.2; 187.5;
230.4; 500; 1000 kbps
Power supply
Nominal supply voltage
24 V AC/DC ±20 % (via pluggable COMBICON screw terminal
block)
Nominal supply voltage
24 V DC ±5 % (as an alternative or redundant, via backplane bus
contact and system current supply)
Typical current consumption
100 mA (24 V DC)
General
Electrical isolation
DIN EN 50178 (VCC // Ethernet // Serial)
Test voltage data interface/data interface
1.5 kV
rms
(50 Hz, 1 min.)
Test voltage data interface/power supply
1.5 kV
rms
Test voltage data interface/power supply
1.5 kV
rms
(50 Hz, 1 min.)
Standards/regulations
EN 50121-4
Electromagnetic compatibility
Conformance with EMC Directive 2004/108/EC
Noise emission
EN 61000-6-4
Net weight
130 g
Housing material
PA 6.6-FR
Color
green
MTBF
666 Years (Telcordia standard, 25°C temperature, 21% operating
cycle (5 days a week, 8 hours a day))
MTBF
179 Years (Telcordia standard, 40°C temperature, 34.25%
operating cycle (5 days a week, 12 hours a day))
MTTF
2013 Years (SN 29500 standard, temperature 25°C, operating
cycle 21% (5 days a week, 8 hours a day))
MTTF
879 Years (SN 29500 standard, temperature 40°C, operating cycle
34.25% (5 days a week, 12 hours a day))
MTTF
359 Years (SN 29500 standard, temperature 40°C, operating cycle
100% (7 days a week, 24 hours a day))
ATEX
 II 3 G Ex nA IIC T4 Gc X
UL, USA
Class I, Zone 2, AEx nA IIC T5
UL, USA / Canada
508 listed
UL, USA / Canada
Class I, Div. 2, Groups A, B, C, D
UL, Canada
Class I, zone 2, Ex nA IIC T5 Gc X
Function
Management
Web-based management, SNMP, emergency exit with Telnet and
serial
Status and diagnostic indicators
LEDs: UL (logic voltage), TD + RD (data activity serial), FD (full
duplex), 100 (100 Mbps mode), Link (Ethernet), Activity (Ethernet),
ERR (error)