Hardware installation
104275_en_c00 PHOENIX CONTACT 2-3
2.1.2 Mounting with DIN rail connectors (connection station)
By using an additional system power supply unit (MINI-SYS-PS-100-240AC/24DC/1.5,
Order No. 2866983), a redundant power supply is made available for further devices con-
nected in the connection station.
Prior to assembly, two DIN rail connectors (Order No. 2709561) for each modem are in-
serted into the DIN rail for forwarding the power supply.
Figure 2-2 Mounting and removal (connection station)
• Push the DIN rail connectors together (A) and insert them into the DIN rail (B/C).
• Place the device onto the DIN rail from above, so that the upper housing keyway hooks
onto the top edge of the DIN rail (D).
• Holding the device by the housing cover, carefully push the device towards the mount-
ing surface so that the device bus connector is securely fixed onto the DIN rail connec-
tor.
• Once the snap-on foot has been snapped onto the DIN rail, check that it is fixed secure-
ly.
Make sure that the DIN rail connector and device are aligned correctly.
• DIN rail connector (plug) left
• Device (snap-on foot) below
B
A
C
D
E