Instructions
Table Of Contents
- Please observe the following notes
- Table of contents
- 1 Description of the SHDSL permanent line modem
- 2 Hardware installation
- 3 Configuration via PSI-CONF
- 4 Optimization
- 5 Eliminating errors
Configuration via PSI-CONF
104275_en_c00 PHOENIX CONTACT 3-11
3.3.1 Setting default settings
3.4 Diagnostics
Diagnostics is only available in online mode.
The diagnostic data of the module, which is connected via USB is displayed.
Reading diagnostic data can be stopped ("Stop reading" button) and restarted ("Read de-
vice status" button).
You can manually reset the diagnostic LED using the "Reset DIAG LED" button.
Configuration >> Set default settings
Set default settings This function is only available in online mode.
The device is supplied with the following configuration:
– Line operation
–DSL:
Automatic data rate detection in the range from 192 kbps to 5.696 Mbps per channel
DSL port A: active
DSL port B: active
– Serial interface:
RS-232 activated, 19.2 kbps, no flow control, 8N1 (8 data bits, no parity, 1 stop bit)
RS-485 deactivated
RS-422 deactivated
– Digital switching outputs:
DSL A, DO = "24 V", in the case of "good to very good connection"
DSL A, DO = "open", in the case of "no or only moderately good connection"
DSL B, DIO = "24 V", in the case of "good to very good connection"
DSL B, DIO = "open", in the case of "no or only moderately good connection"