Eliminating errors
104275_en_c00 PHOENIX CONTACT 5-3
019 Protocol of the serial in-
terface contains too long
frames
ERR LED and
DIAG LED on
A frame-oriented transmission
was configured. In this configura-
tion, frames up to a length of 500
characters can be transmitted. But
frames with more than 500 charac-
ters are received.
If the protocol does not con-
tain frames in that length:
Check if the frame end-
time is set correctly.
If the protocol does contain
frames in that length:
Change to character-ori-
ented transmission, if
possible.
020 Too many parity errors on
the serial interface
ERR LED and
DIAG LED on
More than 40 % of the data pack-
ets contain parity errors. This can
be explained only by a misconfigu-
ration.
Check that the following device
settings are correct and match the
data to be transmitted:
–parity
data bits (7 or 8 bits)
stop bits
data rate
021 Too many stop bit errors
on the serial interface
ERR LED and
DIAG LED on
More than 40 % of the data pack-
ets contain stop bit errors. This can
be explained only by a misconfigu-
ration.
Check if the following device set-
tings are correct and match the
data to be transmitted:
–parity
data bits (7 or 8 bits)
stop bits
data rate
022 Data overload on the
SHDSL line
ERR LED and
DIAG LED on
At least temporarily, the transmis-
sion capacity of the SHDSL line is
not large enough. Data can not be
moved as quickly on the SHDSL
line, as they are received.
Reduce the serial data rate
If possible, increase the SHD-
SL data rate
023 Device configuration in-
compatible/inconsistent
ERR LED and
DIAG LED on
The configuration of a neighbor
device is not compatible with the
configuration of this device.
Configure all devices as it is speci-
fied in the relevant configuration
wizard.
024 Massive protocol viola-
tions on the serial inter-
face
ERR LED and
DIAG LED on
On the serial interface there are
many too long periods of "zeros".
Cause:
Incorrect data rate configured
(actual data rate is lower than
that of the device).
A short circuit on the serial
data line.
If RS-422 or RS-485 is used, a
reversed polarity of Line R(N)
and R(P) in RS-422 mode or
Line D(A) and D(B) in RS-485
mode may be the reason, too.
Is the correct data rate confi-
gured?
Wiring of the serial interface
(short circuit?)
A driver of a device connected
to the serial port may be de-
fective
In RS-422/RS-485 mode, seri-
al interface signal lines may be
interchanged (Reversed po-
larity in RS-485 or RS-422
mode)
Table 5-1 Diagnostic IDs
No. Meaning LED Possible cause(s) Remedy