Eliminating errors
104275_en_c00 PHOENIX CONTACT 5-9
201 Interface receives data The specified serial port receives
data. Previously for at least one
minute no data was received.
202 No more collisions on the
RS-485 interface.
Previously, there were collisions
on the specified serial port. Since
one minute no more collisions
were detected.
203 No more parity errors. Previously, there were parity errors
on the specified interface. Since
one minute no more parity errors
were detected.
204 No more stop bit errors. Previously, there were stop bit er-
rors. Since one minute no more
stop bit errors were detected.
205 No overloading of the
SHDSL line anymore.
Previously, data loss has occurred
due to the overload of a SHDSL
line. Since one minute no more
data loss was detected.
206 Data is received from the
SHDSL port.
Data is received from the specified
SHDSL port and sent to the serial
interface. For at least one minute,
this has not been the case.
207 No more inconsistent de-
vice configuration de-
tected.
Previously, an inconsistent device
configuration has been detected.
For one minute, this could not be
detected any more.
Cause: probably link termination.
208 No more noise. Previously, noise has been de-
tected on a serial port. Since one
minute there was no more noise
detected.
209 No protocol violations on
the serial interface any-
more.
Previously, protocol violations
were found on a serial interface.
Since one minute there were no
more protocol violations detected.
210 No overflow of the buffer
detected.
Previously, an overflow in the soft-
ware buffer has occurred. Since
one minute there was no overflow
detected.
Table 5-1 Diagnostic IDs
No. Meaning LED Possible cause(s) Remedy