Datasheet

https://www.phoenixcontact.com/us/produkte/2320018
Nov 13, 20132/5
DC/DC converters-MINI-PS- 12- 24DC/ 5-15DC/2-2320018
Technical data
Input data
Current consumption
2.3 A (12 V DC)
Current consumption
1.1 A (24 V DC)
Inrush surge current
< 10 A (typical)
Power failure bypass
> 4 ms (12 V DC)
Power failure bypass
> 18 ms (24 V DC)
Input fuse
6.3 A (slow-blow, internal)
Output data
Nominal output voltage
12 V DC ±1%
Setting range of the output voltage
5 V DC ... 15 V DC
Output current
2 A (-25 °C ... 60 °C)
Derating
60 °C ... 70 °C (2.5%/K)
Connection in parallel
Yes, for assembling redundant systems and increasing efficiency
Connection in series
Yes
Residual ripple
< 20 mV
PP
(20 MHz)
Peak switching voltages nominal load
< 10 mV
PP
(20 MHz)
Maximum power dissipation NO-Load
< 1 W
Power loss nominal load max.
< 4.2 W
General
Net weight
0.2 kg
Efficiency
> 88 % (at 24 V DC and nominal values)
Insulation voltage input/output
1.5 kV (type test)
Insulation voltage input/output
1 kV (routine test)
Protection class
III
MTBF (IEC 61709, SN 29500)
> 2072000 h (According to EN 29500)
Mounting position
horizontal DIN rail NS 35, EN 60715
Assembly instructions
Can be aligned: Horizontally 0 mm, vertically 50 mm
Electromagnetic compatibility
Conformance with EMC Directive 2004/108/EC
Noise emission
EN 50081-2
Low Voltage Directive
Conformance with LV directive 2006/95/EC
Standard - Electrical safety
EN 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power
installations and their assembly into electrical power
installations
EN 50178/VDE 0160 (PELV)
Standard - Safe isolation
DIN VDE 0100-410
Standard - Safe isolation
DIN VDE 0106-101
UL approvals
UL/C-UL listed UL 508
UL approvals
UL/C-UL Recognized UL 60950
Connection data, input
Connection method
Pluggable screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²