Datasheet

https://www.phoenixcontact.com/us/produkte/2320034
Nov 14, 20132/8
DC/DC converters-QUINT-PS/24DC/24DC/ 5-2320034
Technical data
Input data
Nominal input voltage
24 V DC
Nominal input voltage range
18 V DC ... 32 V DC
Nominal input voltage range
14 V DC ... 18 V DC (Consider derating during operation)
Input voltage range DC
18 V DC ... 32 V DC
Input voltage range DC
14 V DC ... 18 V DC (Consider derating during operation)
Current consumption
7 A (24 V, I
BOOST
)
Inrush surge current
< 15 A (typical)
Power failure bypass
> 10 ms (24 V DC)
Input fuse
15 A (internal (device protection))
Choice of suitable fuses
10 A ... 16 A (Characteristics B, C, D, K)
Type of protection
Transient surge protection
Protective circuit/component
Varistor
Output data
Nominal output voltage
24 V DC ±1%
Setting range of the output voltage
18 V DC ... 29.5 V DC (> 24 V constant capacity)
Output current
5 A (-25 °C ... 60 °C)
Output current
6.25 A (with POWER BOOST, -25°C ... 40°C permanently, U
OUT
=
24 V DC)
Output current
30 A (SFB technology, 12 ms)
Magnetic fuse tripping
B2
Magnetic fuse tripping
B4
Magnetic fuse tripping
C2
Derating
60 °C ... 70 °C (2.5%/K)
Connection in parallel
Yes, for redundancy and increased capacity
Connection in series
Yes
Max. capacitive load
Unlimited
Current limitation
Approximately 7.2 A
Control deviation
< 1 % (change in load, static 10% ... 90%)
Control deviation
< 2 % (change in load, dynamic 10% ... 90%)
Control deviation
< 0.1 % (change in input voltage ±10%)
Residual ripple
< 20 mV
PP
Peak switching voltages nominal load
< 10 mV
PP
(20 MHz)
Maximum power dissipation NO-Load
2.4 W
Power loss nominal load max.
11.4 W
General
Net weight
0.7 kg
Efficiency
> 92 %
Insulation voltage input/output
1.5 kV (type test)
Insulation voltage input/output
1 kV (routine test)
Protection class
III