Datasheet

https://www.phoenixcontact.com/us/products/2320115
03/14/2018Page2/11
DC/DC converters-QUINT-PS/24DC/12DC/ 8-2320115
Technical data
Dimensions
Width 32 mm
Height 130 mm
Depth 125 mm
Width with alternative assembly 122 mm
Height with alternative assembly 130 mm
Depth with alternative assembly 35 mm
Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C derating, 2.5 %/K, startup at -40°C type-tested)
Ambient temperature (start-up type tested) -40 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Climatic class 3K3 (in acc. with EN 60721)
Degree of pollution 2
Input data
Nominal input voltage range 24 V DC
Input voltage range 18 V DC ... 32 V DC
Current consumption
6 A (24 V, I
BOOST
)
Inrush surge current < 15 A (typical)
Mains buffering > 10 ms (24 V DC)
Input fuse 15 A (internal (device protection))
Type of protection Transient surge protection
Protective circuit/component Varistor
Output data
Nominal output voltage 12 V DC ±1%
Setting range of the output voltage (U
Set
)
5 V DC ... 18 V DC (> 12 VDC, constant capacity restricted)
Nominal output current (I
N
)
8 A (-25°C ... 60°C)
POWER BOOST (I
Boost
) 10 A (-25°C...40°C permanent, U
OUT
= 12VDC )
Selective Fuse Breaking (I
SFB
)
48 A (12 ms)
Derating 60 °C ... 70 °C (2.5%/K)
Connection in parallel Yes, for redundancy and increased capacity
Connection in series yes
Feedback resistance 25 V DC
Circuit breaker against surge voltage at output by invasive foreign matter Yes, limited to < 25 V DC
Max. capacitive load Unlimited
Active current limitation 15 A