Datasheet

https://www.phoenixcontact.com/us/products/2320115
03/14/2018Page4/11
DC/DC converters-QUINT-PS/24DC/12DC/ 8-2320115
Technical data
Connection data, output
Conductor cross section AWG max. 12
Stripping length 7 mm
Screw thread M3
Connection data for signaling
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Screw thread M3
Standards and Regulations
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Noise immunity EN 61000-6-2:2005
Connection in acc. with standard CUL
Standards/regulations EN 61000-4-2
Contact discharge 4 kV (Test Level 2)
Standards/regulations EN 61000-4-3
Frequency range 80 MHz ... 1 GHz
Test field strength 10 V/m
Frequency range 1.4 GHz ... 2 GHz
Test field strength 3 V/m
Standards/regulations EN 61000-4-4
Comments Criterion B
Standards/regulations EN 61000-4-5
Signal 1 kV (Test Level 2 - asymmetrical)
Standards/regulations EN61000-6-3
EN61000-4-6
Frequency range 0.15 MHz ... 80 MHz
Voltage 10 V (Test Level 3)
Standard - Electrical safety EN 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power installations
and their assembly into electrical power installations
EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage EN 60950-1 (SELV)
EN 60204 (PELV)
Standard - Safe isolation DIN VDE 0100-410
Shipbuilding approval DNVGL(EMCB)