Datasheet

https://www.phoenixcontact.com/us/products/2320115
03/14/2018Page5/11
DC/DC converters-QUINT-PS/24DC/12DC/ 8-2320115
Technical data
Standards and Regulations
UL approvals UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous
Location)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.
Rail applications EN 50121-4
Environmental Product Compliance
China RoHS Environmentally Friendly Use Period = 25;
For details about hazardous substances go to tab “Downloads”, Category
“Manufacturer's declaration”
Drawings
Block diagram
DCOK
U >19,2V
IN
I<I
N
+
+
+
-
-
-
-
Classifications
eCl@ss
eCl@ss 4.0 27250311
eCl@ss 4.1 27250311
eCl@ss 5.0 27242213
eCl@ss 5.1 27242213
eCl@ss 6.0 27049005
eCl@ss 7.0 27210901
eCl@ss 8.0 27210901
eCl@ss 9.0 27210901
ETIM
ETIM 4.0 EC002542