Datasheet

https://www.phoenixcontact.com/us/produkte/2320186
Nov 14, 20132/6
Redundancy module-QUINT-ORING/24DC/2X20/1X40-2320186
Technical data
Input data
Type of protection
Protection against static surge voltages > 30 V
Nominal input current I
N
2x 20 A (-25 °C ... 60 °C)
Nominal input current I
N
1x 40 A (-25 °C ... 60 °C)
Maximum current I
max
2x 26 A (-25°C ... 40°C)
Maximum current I
max
1x 52 A (-25°C ... 40°C)
Output data
Nominal output voltage
0.2 V (< DC input)
Output current
40 A (Increasing power)
Output current
20 A (Redundancy)
Derating
60 °C ... 70 °C (2.5%/K)
Power loss nominal load max.
8 W (I
OUT
= 40 A)
General
Net weight
0.6 kg
Efficiency
> 98 %
Protection class
III
MTBF (IEC 61709, SN 29500)
> 720000 h (According to EN 29500)
Mounting position
horizontal DIN rail NS 35, EN 60715
Assembly instructions
Alignable: 5 mm horizontally, 15 mm next to active components,
50 mm vertically
Electromagnetic compatibility
Conformance with EMC Directive 2004/108/EC
Low Voltage Directive
Conformance with LV directive 2006/95/EC
Standard – Electrical equipment of machines
EN 60204
Standard - Electrical safety
EN 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power
installations and their assembly into electrical power
installations
EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage
IEC 60950-1 (SELV) and EN 60204 (PELV)
UL approvals
UL/C-UL listed UL 508
UL approvals
UL/C-UL Recognized UL 60950
UL approvals
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D
(Hazardous Location)
Connection data, input
Connection method
Screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
6 mm²
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
4 mm²
Conductor cross section AWG/kcmil min.
10
Stripping length
8 mm
Screw thread
M3
Connection data, output