Energy storage-UPS-BAT/VRLA/24DC/12AH-2320322
Technical data
Output data
Output current I
max
50 A
Connection in parallel 5
Connection in series No
Output fuse 2x 25 A
General
IQ technology Yes
Disposal
Used batteries must not be thrown away with household waste, they
should instead be disposed of in accordance with applicable national
regulations. They can also be returned to Phoenix Contact or the
manufacturer.
Net weight 8.9 kg
Memory medium Lead rechargeable battery module
Protection class III
Mounting position horizontal DIN rail NS 35, EN 60715
Standards and Regulations
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Connection in acc. with standard CUL
Standard - Electrical safety EN 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power installations
and their assembly into electrical power installations
EN 50178/VDE 0160 (PELV)
Shipbuilding approval Germanischer Lloyd (EMC 2), ABS, DNV
UL approvals UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D
(Hazardous Location)
VdS approval G 100001
Vibration (operation)
< 15 Hz, amplitude ±2.5 mm, 15 - 150 Hz, 2.3g/2.3g according to IEC
60068-2-6
15 Hz ... 150 Hz, 2.3g, 90 min.
Drawings
Block diagram
Battery
DC 24V
m
C
J
12V
12V