Data Sheet

Technical Data
Input data
AC operation
Nominal input voltage range 3x 400 VAC ... 500 VAC
3x 320 VAC ... 575 VAC
2x 360 VAC ... 575 VAC (Not approved by UL)
Input voltage range
450 VDC ... 800 VDC
3x 320 VAC ... 575 VACInput voltage range AC
2x 360 VAC ... 575 VAC (Not approved by UL)
Input voltage range DC 450 VDC ... 800 VDC
Voltage type of supply voltage AC/DC
Inrush current < 20 A (typical)
Inrush current integral (I
2
t) < 1 A
2
s
AC frequency range 45 Hz ... 65 Hz
Frequency range DC 0 Hz
typ. 25 ms (400VAC)Mains buffering time
typ. 35 ms (500 VAC)
3x 2.1 A (400VAC)
3x 1.7 A (500 VAC)
Current consumption
1.7 A (600 VDC)
Nominal power consumption 1386 VA
Protective circuit Transient surge protection; Varistor
Typical response time < 1 s
Permissible backup fuse B6 B10 B16 AC:
Permissible DC backup fuse DC: Connect a suitable fuse upstream
Recommended breaker for input protection 6 A ... 16 A (AC: Characteristics B, C, D, K)
Discharge current to PE < 3.5 mA
Output data
Efficiency > 93 % (at 400 V AC and nominal values)
Nominal output voltage 48 VDC ±1%
Setting range of the output voltage (U
Set
) 30 VDC ... 56 VDC (> 48VDC, constant capacity restricted)
Nominal output current (I
N
) 20 A (-25°C...60°C, U
OUT
= 48VDC)
POWER BOOST (I
Boost
) 22.5 A (-25°C...40°C permanent, U
OUT
= 48VDC )
Selective Fuse Breaking (I
SFB
) 100 A (12 ms)
Magnetic circuit breaker tripping B2 / B4 / B6 / B10 / C2 / C4 / C6
Derating 60 °C ... 70 °C (2.5%/K)
Feedback voltage resistance max. 60 VDC
Protection against overvoltage at the output (OVP) < 60 VDC
Active current limitation Approx. I
BOOST
= 22.5 A (for short-circuit)
< 1 % (change in load, static 10 % ... 90 %)
< 4 % (change in load, dynamic 10 % ... 90 %)
Control deviation
Power supply unit - QUINT-PS/3AC/48DC/20
2320827