Data Sheet
Technical Data
Input data
AC operation
Nominal input voltage range 3x 400 VAC ... 500 VAC
3x 320 VAC ... 575 VAC
2x 360 VAC ... 575 VAC (Not approved by UL)
Input voltage range
450 VDC ... 800 VDC
3x 320 VAC ... 575 VACInput voltage range AC
2x 360 VAC ... 575 VAC (Not approved by UL)
Input voltage range DC 450 VDC ... 800 VDC
Voltage type of supply voltage AC/DC
Inrush current < 20 A (typical)
Inrush current integral (I
2
t) < 1 A
2
s
AC frequency range 45 Hz ... 65 Hz
Frequency range DC 0 Hz
typ. 25 ms (400VAC)Mains buffering time
typ. 35 ms (500 VAC)
3x 2.1 A (400VAC)
3x 1.7 A (500 VAC)
Current consumption
1.7 A (600 VDC)
Nominal power consumption 1386 VA
Protective circuit Transient surge protection; Varistor
Typical response time < 1 s
Permissible backup fuse B6 B10 B16 AC:
Permissible DC backup fuse DC: Connect a suitable fuse upstream
Recommended breaker for input protection 6 A ... 16 A (AC: Characteristics B, C, D, K)
Discharge current to PE < 3.5 mA
Output data
Efficiency > 93 % (at 400 V AC and nominal values)
Nominal output voltage 48 VDC ±1%
Setting range of the output voltage (U
Set
) 30 VDC ... 56 VDC (> 48VDC, constant capacity restricted)
Nominal output current (I
N
) 20 A (-25°C...60°C, U
OUT
= 48VDC)
POWER BOOST (I
Boost
) 22.5 A (-25°C...40°C permanent, U
OUT
= 48VDC )
Selective Fuse Breaking (I
SFB
) 100 A (12 ms)
Magnetic circuit breaker tripping B2 / B4 / B6 / B10 / C2 / C4 / C6
Derating 60 °C ... 70 °C (2.5%/K)
Feedback voltage resistance max. 60 VDC
Protection against overvoltage at the output (OVP) < 60 VDC
Active current limitation Approx. I
BOOST
= 22.5 A (for short-circuit)
< 1 % (change in load, static 10 % ... 90 %)
< 4 % (change in load, dynamic 10 % ... 90 %)
Control deviation
Power supply unit - QUINT-PS/3AC/48DC/20
2320827
https://www.phoenixcontact.com/ae/products/2320827
Dec 16, 2021, 10:49 AM Page 3 (20)