Data Sheet

> 509000 h (40°C)
Insulation characteristics
Protection class I
Degree of pollution 2
Dimensions
Width 96 mm
Height 130 mm
Depth 179 mm
Alternative assembly
Width 176 mm
Height 130 mm
Depth 99 mm
Mounting
Mounting type DIN rail mounting
Assembly instructions alignable: P
N
≥50%, 5mm horizontally, 15mm next to active
components, 50mm vertically
alignable: P
N
<50%, 0mm horizontally, 40mm vertically top, 20
mm vertically bottom
Mounting position horizontal DIN rail NS 35, EN 60715
Material specifications
Housing material Metal
Type of housing Steel sheet, zinc-plated
Housing material Steel sheet, zinc-plated
Environmental and real-life conditions
Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Ambient temperature (start-up type tested) -40 °C
Maximum altitude 4000 m
Climatic class 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Shock 18 ms, 30g, in each space direction (according to IEC60068-2-
27)
< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)Vibration (operation)
15 Hz ... 150 Hz, 2.3g, 90 min.
Standards and regulations
EN50121-4Rail applications
EN50121-3-2
Power supply unit - QUINT-PS/3AC/48DC/20
2320827
https://www.phoenixcontact.com/ae/products/2320827