Datasheet

https://www.phoenixcontact.com/gb/products/2320908
06/18/2019Page5/10
Power supply, with protective coating-QUINT-PS/1AC/24DC/ 5/
CO-2320908
Technical data
Standards and Regulations
Frequency range 0.15 MHz ... 80 MHz
Voltage 10 V (Test Level 3)
Low Voltage Directive Conformance with LV directive 2006/95/EC
Standard - Electrical safety IEC60950-1/VDE0805 (SELV)
Standard – Electronic equipment for use in electrical power installations
and their assembly into electrical power installations
EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage IEC60950-1 (SELV) and EN60204-1 (PELV)
Standard - Safe isolation DIN VDE 0100-410
Standard – Limitation of mains harmonic currents EN61000-3-2
Standard - Equipment safety BG (design tested)
Shipbuilding approval DNVGL(EMCA)
UL approvals UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D
(Hazardous Location)
DeviceNet approval DeviceNet™ Power Supply Conformance Tested
Shock 18 ms, 30g, in each space direction (according to IEC60068-2-27)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.
Approval - requirement of the semiconductor industry with regard to
mains voltage dips
SEMI F47-0706 Compliance Certificate
Certificate
IEC 60950-1 (2
nd
Edition)
Rail applications EN 50121-4
Noxious gas test ISA-S71.04-1985 G3 Harsh Group A
ATEX  II 3 G Ex nA nC IIC T4 Gc
TÜV 11 ATEX 555674 X
IECEx Ex nA nC IIC T4 Gc
IECEx TUN 11.0002X
Overvoltage category (EN 62477-1) III
Environmental Product Compliance
Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 25;
For details about hazardous substances go to tab “Downloads”,
Category “Manufacturer's declaration”
Drawings