Datasheet

https://www.phoenixcontact.com/us/products/2866763
03/07/2018Page5/14
Power supply unit-QUINT-PS/1AC/24DC/10-2866763
Technical data
Standards and Regulations
Test field strength 10 V/m (Test Level 3)
Frequency range 1.4 GHz ... 2 GHz
Test field strength 3 V/m (Test Level 2)
Standards/regulations EN 61000-4-4
Comments Criterion B
Standards/regulations EN 61000-4-5
Signal 1 kV (Test Level 2 - asymmetrical)
Standards/regulations EN61000-6-3
EN61000-4-6
Frequency range 0.15 MHz ... 80 MHz
Voltage 10 V (Test Level 3)
Low Voltage Directive Conformance with LV directive 2006/95/EC
Standard - Electrical safety IEC 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power installations
and their assembly into electrical power installations
EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage IEC 60950-1 (SELV) and EN 60204-1 (PELV)
Standard - Safe isolation DIN VDE 0100-410
Standard – Limitation of mains harmonic currents EN 61000-3-2
Standard - Equipment safety BG (design tested)
Standard - Approval for medical use IEC 60601-1, 2 x MOOP
Shipbuilding approval DNVGL(EMCB),ABS, LR, RINA, NK, BV
UL approvals UL Listed UL 508
UL/C-UL Recognized UL 60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous
Location)
DeviceNet approval DeviceNet™ Power Supply Conformance Tested
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.
Approval - requirement of the semiconductor industry with regard to mains
voltage dips
SEMI F47-0706 Compliance Certificate
Information technology equipment - safety (CBscheme)
IEC 60950-1 (2
nd
Edition)
Rail applications EN 50121-4
Overvoltage category (EN 62477-1) III
Environmental Product Compliance
China RoHS Environmentally Friendly Use Period = 25;