Datasheet

https://www.phoenixcontact.com/us/produkte/2688093
Nov 14, 20132/9
Special function module-AXL CNT 2/INC 2-2688093
Technical data
Ambient conditions
Permissible humidity (storage/transport)
5 % ... 95 % (no condensation)
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection
IP20
General
Weight
205 g
Note on weight specifications
with plugs and bus base module
Mounting type
DIN rail
Protection class
III, IEC 61140, EN 61140, VDE 0140-1
Test section
5 V communications power (logic), 24 V supply (I/O) 500 V AC 50
Hz 1 min
Test section
5 V supply (logic)/functional earth ground 500 V AC 50 Hz 1 min
Test section
24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min
Conformance with EMC directives
Noise immunity test in accordance with EN 61000-6-2 Electrostatic
discharge (ESD) EN61000‑4‑2/IEC61000‑4‑2 Criterion B; 6 kV
contact discharge, 8 kV air discharge
Conformance with EMC directives
Noise immunity test in accordance with EN 61000-6-2
Electromagnetic fields EN61000‑4‑3/IEC61000‑4‑3 Criterion A;
Field intensity: 10 V/m
Conformance with EMC directives
Noise immunity test in accordance with EN 61000-6-2 Fast
transients (burst) EN61000‑4‑4/IEC61000‑4‑4 Criterion B, 2kV
Conformance with EMC directives
Noise immunity test in accordance with EN 61000-6-2 Transient
surge voltage (surge) EN61000‑4‑5/IEC61000‑4‑5 Criterion B;
DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical)
Conformance with EMC directives
Noise immunity test in accordance with EN 61000-6-2 Conducted
interference EN61000‑4‑6/IEC61000‑4‑6 Criterion A; Test voltage
10 V
Conformance with EMC directives
Noise emission test according to EN 61000-6-3 Radio interference
properties EN 55022 Class B
Mechanical tests
Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5 g
Mechanical tests
Shock in acc. with EN 60068-2-27/IEC 60068-2-27 30g, 11 ms
period, half-sine shock pulse
Mechanical tests
Continuous shock according to EN60068-2-27/IEC60068-2-27 10
g
Diagnostics messages
Short-circuit / overload of the digital outputs Yes
Diagnostics messages
Error at the symmetrical incremental encoder Yes
Interfaces
Name
AxiolineFlocal bus
Connection method
Bus base module
Transmission speed
100 MBit/s
Axioline potentials
Communications power U
bus
5 V DC (via bus base module)
Current consumption from U
bus
typ. 100 mA
Current consumption from U
bus
max. 120 mA