Datasheet

https://www.phoenixcontact.com/us/produkte/2688093
Nov 14, 20133/9
Special function module-AXL CNT 2/INC 2-2688093
Technical data
Axioline potentials
Supply of digital input modules U
I
24 V DC
Current consumption from U
I
typ. 50.5 mA (Own current consumption; without wiring of the
terminal points)
Current consumption from U
I
max. 2.5 A (dependent on the encoder or sensor type used and
the load on the digital output.)
Counter inputs
Number of inputs
2 (S1, S2)
Description of the input
EN 61131-2, type 3
Connection method
Push-in technology
Input voltage
24 V DC
Input voltage range "0" signal
-3 V DC ... 5 V DC
Input voltage range "1" signal
11 V DC ... 30 V DC
Input frequency
max. 300 kHz /150 kHz (depending on the input voltage)
Input current
2.5 mA (per channel)
Resolution
32
Permissible cable length to the sensor
30 m
Encoder inputs
Input name
Incremental encoder inputs
Number of inputs
2 (A1, /A1, B1, /B1, Z1, /Z1; A2, /A2, B2, /B2, Z2, /Z2)
Connection method
Push-in technology
Encoder signals
Symmetrical and asymmetrical encoders
Cable length
30 m
Encoder data
Number of 5 V encoder supplies
2 (U
E1
, U
E2
)
Nominal output voltage
5 V DC
Voltage range
5 V DC ... 5.5 V DC
Current carrying capacity
max. 250 mA
Type of protection
Short-circuit protection
Protective circuit/component
Electronic
Number of 24 V encoder supplies
2 (U
S1
, U
S2
)
Nominal output voltage
24 V DC
Voltage range
19.2 V DC ... 30 V DC
Current carrying capacity
typ. 500 mA
Type of protection
Short-circuit protection
Protective circuit/component
Electronic
Name
Symmetrical incremental encoders
Encoder types that can be connected
max. 2 (A, /A, B, /B, (Z, /Z))
Type of connection of signals
Push-in technology
Encoder supply voltage
5 V DC
Encoder supply voltage
24 V DC