Datasheet

https://www.phoenixcontact.com/us/produkte/2692322
Nov 13, 20133/10
Bus coupler-IL PB BK DI8 DO4/EF-PAC-2692322
Technical data
System limits of the bus coupler
Number of local bus devices that can be connected
max. 61 (On board I/Os are two devices)
Number of devices with parameter channel
max. 16
Number of branch terminals with remote bus branch
0
Response time of I/Os
typ. 4 ms (aligned I/Os; transmission speed: PROFIBUS 1.5 Mbps,
local bus 500 kbps)
Power supply for module electronics
Connection method
Spring-cage connection
Name
Bus coupler supply U
BC
; Communications power U
L
(7.5V) and
the analog supply U
ANA
(24 V) are generated from the bus coupler
supply.
Supply voltage
24 V DC (via Inline plug)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current consumption
max. 0.98 A (from U
BK
)
Communications power U
L
7.5 V DC
Current consumption
0.8 A
Power consumption
typ. 1.7 W
Inline potentials
Communications power U
L
7.5 V DC ±5 %
Power supply at U
L
max. 0.8 A DC
Main circuit supply U
M
24 V DC
Supply voltage range U
M
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply at U
M
max. 8 A DC (Sum of U
M
+ U
S
)
Current consumption from U
M
max. 8 A DC
Segment supply voltage U
S
24 V DC
Supply voltage range U
S
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply at U
S
max. 8 A DC (Sum of U
M
+ U
S
)
Current consumption from U
S
max. 8 A DC
I/O supply voltage U
ANA
24 V DC
Supply voltage range U
ANA
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply at U
ANA
max. 0.5 A DC
Digital inputs
Input name
Digital inputs
Connection method
Inline plugs
Connection method
2, 3-wire
Number of inputs
max. 8 (EN 61131-2 type 1)
Typical response time
approx. 500 µs
Protective circuit
Protection against polarity reversal Polarity protection diode
Input voltage
24 V DC
Input voltage range "0" signal
-30 V DC ... 5 V DC
Input voltage range "1" signal
15 V DC ... 30 V DC