Datasheet

https://www.phoenixcontact.com/us/produkte/2692380
Nov 13, 20133/10
Bus coupler-IL S3 BK DI8 DO4 2TX-PAC-2692380
Technical data
System limits of the bus coupler
Amount of process data
max. 4096 Byte (per station)
Number of supported devices
max. 63 (per station)
Number of local bus devices that can be connected
max. 61 (On board I/Os are two devices)
Number of devices with parameter channel
max. 16
Number of branch terminals with remote bus branch
0
Power supply for module electronics
Connection method
Spring-cage connection
Name
Bus coupler supply U
BC
; Communications power U
L
(7.5V) and
the analog supply U
ANA
(24 V) are generated from the bus coupler
supply.
Supply voltage
24 V DC (via Inline plug)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Supply current
max. 150 mA
Current consumption
max. 1.05 A (from U
BK
)
Power loss
typ. 3.2 W (Entire device)
Communications power U
L
7.5 V DC
Current consumption
0.8 A
Power consumption
typ. 1.7 W
Inline potentials
Communications power U
L
7.5 V DC ±5 %
Power supply at U
L
max. 0.8 A DC
Main circuit supply U
M
24 V DC
Supply voltage range U
M
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply at U
M
max. 8 A DC (Sum of U
M
+ U
S
)
Current consumption from U
M
max. 8 A DC
Segment supply voltage U
S
24 V DC
Supply voltage range U
S
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply at U
S
max. 8 A DC (Sum of U
M
+ U
S
)
Current consumption from U
S
max. 8 A DC
I/O supply voltage U
ANA
24 V DC
Supply voltage range U
ANA
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply at U
ANA
max. 0.5 A DC
Digital inputs
Input name
Digital inputs
Connection method
Inline plugs
Connection method
2, 3-wire
Number of inputs
max. 8 (EN 61131-2 type 1)
Typical response time
approx. 500 µs
Protective circuit
Protection against polarity reversal Polarity protection diode
Input voltage
24 V DC