Alarm outputs
Number of outputs 1 (digital, PNP)
Voltage 22 V DC (U
s
-2V)
Current max. 100 mA
Maximum inrush current 500 mA (t=1ms at U
s
)
Short-circuit protection no
General data
Relay type Electromechanically forcibly guided, dust-proof relay.
Nominal operating mode 100% operating factor
Degree of protection IP20
Min. degree of protection of inst. location IP54
Mounting type DIN rail mounting
Mounting position vertical, horizontal, with front of module upward
Assembly instructions See derating curve
Dimensions (W/H/D) 6.8 x 93.1 x 102.5 mm
Type of housing PBT yellow
Clearances and creepage distances between the power circuits DINEN50178, EN60079-15
Rated insulation voltage 250 V AC
Rated surge voltage/insulation Safe isolation, reinforced insulation 6kV from control circuit, start circuit, signal
output to the enabling current path; 4 kV / basic insulation between all current
paths and housing
Pollution degree 2
Surge voltage category III
Connection data
Connection method Screw connection
Conductor cross section, solid 0.2 mm² ... 2.5 mm²
Conductor cross section, stranded 0.2 mm² ... 2.5 mm²
Conductor cross section AWG/kcmil 26 ... 12
Stripping length 12 mm
Screw thread M3
Ambient conditions
Ambient temperature (operation) -40 °C ... 70 °C (observe derating)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) 75 % (on average, 85% infrequently, non-condensing)
Max. permissible humidity (storage/transport) 75 % (on average, 85% infrequently, non-condensing)
Maximum altitude max. 2000 m (Above sea level)
Shock 15g
Vibration (operation) 2g
Conformance / approvals
Conformance CE-compliant
Approvals
UL, USA / Canada ( E140324 ) cULus
UL, USA / Canada ( E360692 ) Class I, Zone 2, AEx nA nC IIC T4 / Ex nA nC IIC Gc T4 X
Shipbuilding GL applied for
Functional Safety in accordance with IEC 61508 to SIL 3