Datasheet

PSR-MC30
106173_en_01 PHOENIX CONTACT 3
Description Type Order No. Pcs. / Pkt.
Safety relay for emergency stop and safety doors up to SIL3, SILCL3,
Cat.4, PLe, 2-channel operation, automatic or manual, monitored start,
cross-circuit detection, 2 enabling current paths, U
S
=24VDC, plug-in
screw terminal block
PSR-MC30-2NO-1DO-24DC-SC 2700498 1
Safety relay for emergency stop and safety doors up to SIL3, SILCL3,
Cat.4, PLe, 2-channel operation, automatic or manual, monitored start,
cross-circuit detection, 2 enabling current paths, U
S
=24VDC, plug-in
spring-cage terminal block
PSR-MC30-2NO-1DO-24DC-SP 2700499 1
3Ordering data
4 Technical data
Hardware/firmware version
HW/FW 00/-- (The technical data and safety characteristics are valid as of the specified
HW/FW version.)
Input data
Rated control supply voltage U
S
24 V DC -15 % / +10 %
Rated control supply current I
S
typ. 65 mA
Typical inrush current 4 A (t=200s at U
s
)
< 20 mA (with U
s
/I
x
to S12)
< 200 mA (with U
s
/I
x
to S34)
< 5 mA (with U
s
/I
x
to S22)
> -15 mA (with U
s
/I
x
to S22/S21)
Current consumption < 5 mA (with U
s
/I
x
to S12)
< 5 mA (with U
s
/I
x
to S22)
> -5 mA (with U
s
/I
x
to S34)
> -5 mA (with U
s
/I
x
to S22/S21)
< 10 mA (with U
s
/I
x
to S34)
Power consumption at U
S
typ. 1.56 W
Voltage at input/start and feedback circuit 24 V DC -15 % / +10 %
Filter time 1 ms (at A1 in the event of voltage dips at U
s
)
max. 1.5 ms (at S12, S22; test pulse width)
min. 7.5 ms (at S12, S22; test pulse rate)
Test pulse rate=5xTest pulse width
Max. permissible overall conductor resistance
(Input and reset circuit at U
S
)
150
Typical response time at U
s
< 175 ms (automatic start)
< 175 ms (manual, monitored start)
Typical starting time with U
s
< 250 ms (when controlled via A1)
Typical release time with U
s
< 20 ms (when controlled via A1 or S12 and S22.)
Recovery time < 500 ms
Maximum switching frequency 0.5 Hz
Operating voltage display 1 x green LED
Status display 3 x green LED
Protective circuit Surge protection Suppressor diode
Reverse polarity protection for rated control supply voltage
Output data
Contact type 2 enabling current paths
Contact material AgSnO
2
Minimum switching voltage 20 V AC/DC
Maximum switching voltage 250 V AC/DC
Limiting continuous current 6 A (N/O contact)