Datasheet

PSR-MC30
106173_en_01 PHOENIX CONTACT 5
Conformance / approvals
Conformance CE-compliant
Approvals $
Safety data
Stop category according to IEC 60204 0
Safety parameters for IEC 61508 - High demand
SIL 3
PFH
d
1.5 x 10
-9
(4ADC13; 5AAC15; 8760switching cycles/year)
Demand rate < 12 Months
Proof test interval 240 Months
Duration of use 240 Months
Safety parameters for IEC 61508 - Low demand
SIL 3
PFD
avg
1.47 x 10
-4
Proof test interval 60 Months
Duration of use 240 Months
Safety parameters for EN 62061
SIL CL 3
Safety characteristic data according to EN ISO 13849
Category 4
Performance level e (4ADC13; 5AAC15; 8760switching cycles/year)
Duration of use 240 Months
For applications in PLe, the required demand rate for the safety function is once per month.