Datasheet

PSR-MC34
106174_en_01 PHOENIX CONTACT 15
15.4 Safety door monitoring/automatic start/without
cross-circuit detection
Two-channel safety door monitoring
Automatic start
No cross-circuit detection in the sensor circuit
Suitable up to category4, PLe (ENISO13849-1),
SILCL3 (EN62061), if cross-circuits in the control to
the actuator and the sensor circuit can be ruled out
Figure 15 Safety door monitoring/automatic start/without
cross-circuit detection
15.5 Single-channel safety door monitoring/
automatic start
Single-channel safety door monitoring
Automatic start
No cross-circuit detection in the sensor circuit
Suitable up to category1, PLc (ENISO13849-1),
SILCL1(EN62061)
Figure 16 Single-channel safety door monitoring/auto-
matic start
15.6 Safety door monitoring/manual, monitored
start
Two-channel safety door monitoring
Manual, monitored start
Suitable up to category4, PLe (ENISO13849-1),
SILCL3 (EN62061), if cross-circuits in the control to
the actuator can be ruled out
Figure 17 Safety door monitoring/manual, monitored
start
15.7 Safety door monitoring/manual, monitored
start/without cross-circuit detection
Two-channel safety door monitoring
Manual, monitored start
No cross-circuit detection in the sensor circuit
Suitable up to category4, PLe (ENISO13849-1),
SILCL3 (EN62061), if cross-circuits in the control to
the actuator and the sensor circuit can be ruled out
Figure 18 Safety door monitoring/manual, monitored
start/without cross-circuit detection
K1
K2
M
24V
K1
K2
N
L
A1
A2
13
14
PSR-MC34
S12
S22
( )
M1
( )
23
24
S11
(+) ( )
34
S34
( )
0V
K2
K1
B1
open
closed
B2
K1
K2
M
24V
K1
K2
N
L
B1
open
A1
A2
13
14
PSR-MC34
S12
S22
( )
M1
( )
23
24
S11
(+) ( )
34
closed
S34
( )
0V
K2
K1
K1
K2
M
24V
K1
K2
N
L
0V
K1
K2
S2
B1
open
closed
B2
A1
A2
13
14
PSR-MC34
S12
S22
( )
M1
( )
23
24
S11
(+) ( )
34
S34
( )
K1
K2
M
24V
K1
K2
N
L
0V
A1
A2
13
14
PSR-MC34
S12
S22
( )
M1
( )
23
24
S11
(+) ( )
34
S34
( )
K1
K2
S2
B1
open
closed
B2