Datasheet

PSR-PC40
106256_en_00 PHOENIX CONTACT 3
Description Type Order No. Pcs. / Pkt.
Coupling relay for SIL3 high- and low-demand applications, couples digital
output signals to the I/O, 2 enabling current paths, 1 digital signal output,
safe state off applications, test pulse filter, plug-in screw terminal block
PSR-PC40-2NO-1DO-24DC-SC 2700588 1
Coupling relay for SIL3 high- and low-demand applications, couples digital
output signals to the I/O, 2 enabling current paths, 1 digital signal output,
safe state off applications, test pulse filter, plug-in spring-cage terminal
block
PSR-PC40-2NO-1DO-24DC-SP 2700589 1
3Ordering data
4 Technical data
Hardware/firmware version
HW/FW 00/-- (The technical data and safety characteristics are valid as of the specified
HW/FW version.)
Input data
Rated control supply voltage U
S
24 V DC -15 % / +10 %
Rated control supply current I
S
typ. 75 mA
Typical inrush current 400 mA (t<100s at U
s
)
< 10 mA (Y1-Y2)
Current consumption < 5 mA (Y1-Y2)
Power consumption at U
S
typ. 1.8 W
Voltage at input/start and feedback circuit 24 V DC -15 % / +10 % (Y1-Y2)
Filter time max. 2 ms (at A1-A2; test pulse width)
100 ms (at A1-A2; test pulse rate)
Max. permissible overall conductor resistance
(Input and reset circuit at U
S
)
150 (Y1-Y2)
Typical starting time with U
s
< 200 ms (when controlled via A1; automatic start)
Typical release time with U
s
< 35 ms (when controlled via A1)
Recovery time 500 ms
Maximum switching frequency 0.5 Hz
Operating voltage display 1 x yellow LED
Status display 2 x green LEDs
Indication 1 x red LED
Protective circuit Surge protection Suppressor diode
Reverse polarity protection for rated control supply voltage
Output data
Contact type 2 enabling current paths
Contact material AgSnO
2
Minimum switching voltage 20 V AC/DC
Maximum switching voltage 250 V AC/DC
Nominal current 6 A (see to derating)
Limiting continuous current 6 A (N/O contact)
Maximum inrush current 6 A
Inrush current, minimum 3 mA
Sq. Total current 60 A
2
(see to derating)
Switching capacity min. 60 mW
Mechanical service life 10 x 10
6
cycles
Output fuse 6 A gL/gG (N/O contact)
4 A gL/gG (for low-demand applications)