Datasheet

https://www.phoenixcontact.com/us/produkte/2700606
Nov 13, 20131/6
Safety module-IB IL 24 LPSDO 8 V2-PAC-2700606
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in
the user's documentation. Our General Terms of Use for Downloads are valid
(http://download.phoenixcontact.com)
Safety-related digital output module, IP20 protection, for the SafetyBridge system. The module has
four safe digital outputs with two-channel occupancy or 8 safe digital outputs with single-channel
occupancy
Product Description
The safety module is an output module from the Inline product range, designed for use in a SafetyBridge technology system. The safety
module can be used as part of an Inline station at any point within an INTERBUS, DeviceNet™, CANopen
®
, EtherNet/IP™, Sercos,
Modbus, PROFINET or PROFIBUS system. The transmission speed of the safety module can be set to 500 kbaud or 2 Mbaud using
a switch. One transmission speed must be used consistently within a station. The module has four safe digital outputs for two-channel
assignment or eight safe digital outputs for single-channel assignment. Depending on the installation and parameterization, in the
SafetyBridge system the safety module can achieve the following safety integrity:- Up to SIL 3 according to standard EN 61508- Up to
SIL CL 3 according to standard EN 62061- Up to Cat. 4/PL e according to standard EN ISO 13849-1 
Product Features
Generation and monitoring of the SafetyBridge protocol
Processing of the parameterized safety logic
Key commercial data
package_quantity
1
GTIN
4046356585859
Technical data
Note:
Utilization restriction
EMC: class A product, see manufacturer's declaration in the
download area
Dimensions
Width
48.8 mm
Height
119.8 mm
Depth
71.5 mm
Note on dimensions
Housing dimensions
Ambient conditions
Ambient temperature (operation)
-25 °C ... 55 °C
Ambient temperature (storage/transport)
-25 °C ... 70 °C
Permissible humidity (operation)
10 % ... 85 % (Take suitable measures against increased air
humidity within the permitted temperature range.)
Permissible humidity (storage/transport)
10 % ... 85 % (Take suitable measures against increased air
humidity within the permitted temperature range.)
Air pressure (operation)
80 kPa ... 108 kPa (up to 2000 m above sea level)

Summary of content (6 pages)