The PROFINET device supports Identification & Maintenance functions (I&M). General Identification & Maintenance
functions 0 ... 4 can be read via slot 0.
I&M 0 (slot 0)
I&M 1 (slot 0)
I&M 2 (slot 0)
I&M 3 (slot 0)
I&M 4 (slot 0)
I&M data Access / data type Presets
MANUFACTURER_ID Read / 2 bytes B0
hex
(Phoenix Contact GmbH & Co. KG)
ORDER_ID Read / 20 bytes 2701517
SERIAL_Number Read / 16 bytes Stipulated in the product process
HARDWARE_Revision Read / 2 bytes Corresponds to the hardware version of the device
SOFTWARE_Revision Read / 4 bytes Corresponds to the firmware version of the device
REVISION_Counter Read / 2 bytes 0000
hex
(reserved)
PROFILE_ID Read / 2 bytes 4E00
hex
(generic device)
PROFILE_SPECIFIC_TYPE Read / 2 bytes 0003
hex
(IO module)
IM_VERSION Read / 2 bytes 0101
hex
(Version 1.1)
IM_SUPPORTED Read / 2 bytes 001E
hex
(I&M 1 ... 4)
I&M data Access / data type Presets
TAG_FUNCTION Read/write / 32 bytes “20
hex
” (empty)
TAG_LOCATION Read/write / 22 bytes “20
hex
” (empty)
I&M data Access / data type Presets
INSTALLATION_DATE Read/write / 16 bytes “20
hex
” (empty)
RESERVED Read/write / 38 bytes 00
hex
I&M data Access / data type Presets
DESCRIPTOR Read/write / 54 bytes “20
hex
” (empty)
I&M data Access / data type Presets
SIGNATURE Read/write / 54 bytes “20
hex
” (empty)