Instructions

AXL E PN DIO16 M12 6M
8443_en_11 PHOENIX CONTACT 5 / 21
General data
Housing material Zinc die-cast
Weight 750 g
Ambient temperature (operation) -25 °C ... 60 °C
CAUTION: Risk of burns
If the device is used at an ambient temperature above50°C, the contact temperature of metal surfaces may
exceed70°C.
Ambient temperature (storage/transport) -25 °C ... 85 °C
Permissible humidity (operation) 5 % ... 95 %
Permissible humidity (storage/transport) 5 % ... 95 %
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection IP65/67
Protection class III, IEC 61140, EN 61140, VDE 0140-1
Connection data
Connection method M12 connector
Interface PROFINET
Number 2
Designation connection point Copper cable
Connection method M12 fast connection technology
Note on connection method D-coded
Number of positions 4
Transmission speed 100 MBit/s (with autonegotiation)
PROFINET
Equipment type PROFINET Device
Conformance class B
Update rate 1 ms
Number of supported application relationships (AR) 2
PROFINET protocols LLDP, MRP client, DCP, DCE-RPC
Additional protocols SNMP v1, HTTP, TFTP, FTP
Supply: Module electronics, sensors and actuators (U
S
)
Connection method M12 connector (T-coded)
Number of positions 4
Supply voltage 24 V DC
Nominal supply voltage range 18 V DC ... 31.2 V DC (including all tolerances, including ripple)
Current consumption typ. 190 mA ±15 % (at 24 V DC)
max. 12 A