Datasheet

https://www.phoenixcontact.com/us/products/2702924
May 3, 20172/5
Extension module-PSR-SCP-42-230UC/
URM4/4NO/2NC-2702924
Technical data
Input data
Rated control circuit supply voltage U
S
42 V AC/DC ... 230 V AC/DC -15 % ... +10 % (Rated control circuit
supply voltage U
S
)
Rated control supply current I
S
typ. 35 mA (42 V DC)
Rated control supply current I
S
typ. 15 mA (230 V AC)
Power consumption at U
S
max. 1.5 W (with DC)
Power consumption at U
S
max. 1.7 W (with AC)
Inrush current
< 38 A (Δt=50µs at U
s
)
Typ. starting time with U
s
< 100 ms (when controlled via A1)
Typical release time
< 20 ms (Control via A1 at 42VDC)
Typical release time
< 200 ms (Control via A1 at 230VAC)
Recovery time
< 1 s
Maximum switching frequency
0.5 Hz
Output data
Contact type
4 enabling current paths
Contact type
1 confirmation current path
Contact type
1 signaling current path
Contact material
AgSnO
2
Minimum switching voltage
5 V AC/DC
Maximum switching voltage
250 V AC/DC (Observe the load curve)
Limiting continuous current
6 A (N/O contact, pay attention to the derating)
Limiting continuous current
1 A (N/C contact 51/52)
Limiting continuous current
6 A (N/C contact 61/62)
Inrush current, minimum
10 mA
Maximum inrush current
8 A
Sq. Total current
72 A
2
(observe derating)
Interrupting rating (ohmic load) max.
1500 VA (N/O contact, 250 V AC, τ = 0 ms)
Interrupting rating (ohmic load) max.
For additional values, see load curve
Maximum interrupting rating (inductive load)
48 W (N/O contact, 24 V DC, τ = 40 ms)
Maximum interrupting rating (inductive load)
40 W (N/O contact, 48 V DC, τ = 40 ms)
Maximum interrupting rating (inductive load)
36 W (N/O contact, 60 V DC, τ = 40 ms)
Maximum interrupting rating (inductive load)
35 W (N/O contact, 110 V DC, τ = 40 ms)
Maximum interrupting rating (inductive load)
33 W (N/O contact, 220 V DC, τ = 40 ms)
Maximum interrupting rating (inductive load)
1500 VA (N/O contact, 250 V AC, τ = 40 ms)
Switching capacity
min. 50 mW
Switching capacity according to IEC 60947-5-1
5 A (24 V (DC13))
Switching capacity according to IEC 60947-5-1
5 A (250 V (AC15))
Output fuse
6 A gL/gG (N/O contact and N/C contact 61/62)
Output fuse
4 A gL/gG (N/O contact and N/C contact 61/62 for low-demand
applications)
Output fuse
1 A gL/gG (N/C contact 51/52)